You are here:
Homepage » Research Programmes » Generation, transmission, distribution and use of electrical energy » Laboratories » Laboratory of electrical energy quality and EMC » Precision wattmeter and analyzer ZES ZIMMER LMG95
- One-power channel wattmeter and analyzer, 1xU+1xI,
- Voltage ranges: 6-600 V,
- Current ranges: 150 mA – 20 A (direct input),
- Frequency bandwidth: DC 50 kHz,
- Basic accuracy: 0.03 %,
- DFT analyzer, , harmonics and interharmonics measurement up to 50 kHz/1 MHz with step of 1 Hz, frequency analysis according to the IEC 61000-4-7, measurement of harmonic current emissions according to IEC 61000-3-2 and 3-12,
- Flicker measurement acc. to the IEC 61000-4-15, tests according to IEC 61000-3-3 and 3-11.